We Produce a wide range of Cables required in different categories. Some of our Products are as follows

We also produce special type of Cables as per reqirement of customer.

_____________________________________________________________
Networking Cable / LAN / CAT 5E / CAT 6

LAN Cable Cat 5E / Cat 6 generally to TIA/EIA 568 A/B specially developed for outdoor applications with moisture barrier tape protects Cables from moisture as well as weather conditions. This cable is also ideal for indoor application

Electrical Performance
 Input Impedance 100 ohm ± 15 ohms      0.772≤freq≤100
               ± 22 ohms      100 ≤ freq ≤200
 Capacitance   4.6 nF / 100 m Nominal
 DC Resistance/Unbalance  9.38 ohms / 100 m Max / 2.5 % Max
 Nom. Velocity of Propagation  71 %
 Dielectric Breakdown  2500 Volts DC Conductor to Conductor
 Propagation Delay  4.59 nSec/m Max @ 10 Mhz
 Propagation Delay Skew  15 nSec / 100 mMax
Mechanical Specification
Nominal Jacket OD 0.195 inch
Nominal Jacket Thickness 0.020 inch
Jacket Minimum Spot Thickness 0.016 inch
Installation Temparature 0° C to 60° C
Operation Temparature -20° C to 60° C
Telephone Cables

Armoured & Unarmoured to ITI/DOT specifications. Unarmoured cables is suitable for use in Indoor Permanent Installations, Telephone Exchanges & Communication Equipments situated in tropical and non-tropical locations.Armoured Cables due to its mechanical strength is suitable for Outdoor & Indoor places .

PVC Sheathed Switchboard Cables.
Conductor
Solid annealed plain or copper wire
Insulation
Hard grade PVC with nominal radial thickness according to table.
Twinning
Two, Three or Four insulated conductors are uniformly twisted together.
Stranding
The pairs, triples or quads are stranded in concentric layers and the Cable core is wrapped with PVC / Polyester tape. An aluminium myler may be wrapped over the stranding pairs, triples or quads if ordered for screening purpose.
Rip Cord
A non-metallic suitable ripcord shall be laid-up longitudinally under the sheath.
Sheath
PVC / Thickness as related specifications.
Application
These type of Switch Board Unarmoured cables is suitable for use in Indoor permanent installations, telephone exchanges, and communication equipment suited in both tropical and non-tropical Locations.
PVC Insulated PVC Sheathed Armoured Telephone Cables.
Conductor
Solid annealed plain or copper wire
Insulation
Hard grade PVC with nominal radial thickness according to table.
Twinning
Two, Three or Four insulated conductors are uniformly twisted together.
Stranding
The pairs, triples or quads are stranded in concentric layers and the Cable core is wrapped with PVC / Polyester tape. An aluminium myler may be wrapped over the stranding pairs, triples or quads if ordered for screening purpose.
Sheath
PVC / Thickness as related specifications.
Armouring
A Covering of Steel round / flat wire over the sheathing applied, as per IS: 1554 / Pt.I / 88 .
Overall Sheath
A heavy PVC sheath applied over the armouring, thickness as per IS: 1554 / Pt.I / 88.
Application
These type of Armoured cables are for Underground purposes due to their mechanical strength, suitable for indoor or outdoor places, for Telephone Exchanges and communication equipment situated in both Tropical and Non-Tropical locations.
Core Dimensions and Resistance as Per I.T.D. Spn. S/WS - 114 - C.
Type
Nominal Dia of Conductor(mm)
Maximum Resistance at 20° C (ohms/km)

Radial thickness of PVC Insulation (mm)

Maximum Dia of Insulated conductor (mm)
A.
0.50
91.00
0.20 + 0.05 or -0.02
1.00
B.
0.60
57.00
0.25 + 0.05 or -0.02
1.24
C.
0.71
45.70
0.28 + 0.05 or -0.02
1.37
D.
0.90
28.45
0.33 + 0.05 or -0.02
1.66
E.
1.12
18.64
0.41 + 0.05 or -0.02
2.04
Electrical Data ( Conductor )
Conductor Diameter
Maximum Conductor Resistance at 20° C.
Minimum Elongation.
0.50 mm
92.2 Ohms/km.
15 %
0.60 mm
64.0 Ohms/km.
15 %
0.71 mm (+/- 0.0127 mm)
45.7 Ohms/km.
20 %
Electrical Data ( Insulation )
Insulation Resistance
Insulation Resistance of finished cables 5 M.ohms/km at 50° C between two insulated conductors.
Spark Test Voltage 3000 Volts ( RMS )
High Voltage Test
3 kV DC or 2 kV RMS between each conductor and remaining conductors bunched and earthed.
Packing & Delivery
The Switch board cables will be delivered in 100 Mtrs length or as ordered. And the armoured cables will be delivered in 500/1000 or as ordered.

 
 

 
 
Armoured Telecommunication cables to ITD-113C (G/WIR-06/02, May94), Armouring to IS:1554 (Part.I) 1988.
No of Pairs
Conductor Diameter (mm)
Overall Dia of Finished Cable.(mm)
Approximate weight of Cables(kg/km)
Conductor Diameter (mm)
Overall Dia of Finished Cables. (mm)
Approximate Weight of Cables. (kg/km)
Standard Drum Length. (m)
1
0.50
9.20
171.000
0.60
9.50
185
1000
2
0.50
10.00
197.000
0.60
10.40
216
1000
3
0.50
10.75
235.000
0.60
10.80
266
1000
4
0.50
11.20
258.000
0.60
11.35
292
1000
5
0.50
12.00
308.000
0.60
12.50
354
1000
10
0.50
13.30
400.000
0.60
14.00
441
1000
15
0.50
14.80
485.000
0.60
15.00
513
1000
20
0.50
16.30
572.000
0.60
16.50
588
1000
25
0.50
17.20
645.000
0.60
17.70
694
500
30
0.50
18.20
710.000
0.60
19.00
785
500
35
0.50
19.10
766.000
0.60
18.50
715
500
40
0.50
18.60
775.000
0.60
19.90
810
500
50
0.50
21.10
840.000
0.60
21.80
960
500
75
0.50
24.40
1100.000
0.60
26.00
1325
500
100
0.50
28.50
1405.000
0.60
29.60
1650
500
200
0.50
37.50
2375.000
0.60
41.10
2900
250
Armoured Telecommunication cables to ITD-114B, Armouring as per IS:1554 (Part.I) 1554/1988.
No of Pairs
Conductor Diameter (mm)
Overall Dia of Finished Cable(mm)
Approximate weight of Cables(kg/km)
Conductor Diameter (mm)
Overall Dia of Finished Cables. (mm)
Approximate Weight of Cables. (kg/km)
Standard Drum Length. (m)
1
0.70
10.00
222
0.90
10.70
258
500
2
0.70
10.75
254
0.90
11.40
293
500
3
0.70
11.50
320
0.90
12.00
329
500
4
0.70
12.40
345
0.90
15.30
475
500
5
0.70
14.30
430
0.90
16.10
530
500
6
0.70
14.70
455
0.90
16.30
550
500
7
0.70
15.00
485
0.90
16.65
585
500
8
0.70
15.60
510
0.90
16.95
615
500
10
0.70
16.50
580
0.90
17.70
675
500
15
0.70
17.65
670
0.90
20.00
725
500
20
0.70
18.75
680
0.90
21.60
910
500
25
0.70
20.00
815
0.90
22.75
1038
500
30
0.70
21.50
885
0.90
24.75
1205
500
35
0.70
23.00
1000
0.90
26.15
1345
500
40
0.70
24.70
1130
0.90
-
-
-
50
0.70
26.50
1290
0.90
32.00
1885
500
75
0.70
32.10
1800
0.90
38.00
2535
250
100
0.70
35.60
2230
0.90
42.70
3215
250
 
Power Cables

Armoured & Unarmoured cables to IS:1554/Pt.I suitable for Generating Stations, Sub-Stations House Service Connections, Street Lighting, Industrial Installation, Building wiring etc.

Various Sizes of Cables as per IS:1554 / Pt.I
Sizes
Cable Code
1. Unarmoured Aluminium conductor / Copper Conductor. Solid / Stranded PVC Insulated PVC Sheathed 1 core.
1.5 Sq.mm to 500 Sq.mm
AYY/YY
2. Unarmoured 2 core / 3 core / 3½ core / 4 core. Aluminium or Copper conductor, Solid / Stranded. PVC insulated PVC Sheathed.
1.5 Sq.mm to 240 Sq.mm
AYY/YY
3. Armoured 2 core / 3 core / 3½ core / 4 core. Aluminium or Copper conductor, Solid / Stranded. PVC insulated, inner armoured with steel wire / strip, Overall PVC Sheathed.
1.5 Sq.mm to 240 Sq.mm

AYWY/AYFY
YWY/YFF

Control Cables

Armoured & Unarmoured Cables to IS:1554/Pt.I, Suitable for Control Purposes or measuring circuits in Generating Stations, Sub-Stations, Industrial Installations as well for Railway Signalling etc.

STARCAB Brand Armoured Control Cable Type - YWY and YFY 650 / 1100 Volts Grade with Copper Conductor - to IS: 1554 / Pt.I
 
Size
 
1. Armoured Control Cable PVC Insulated, PVC Inner Armoured with steel wire / strip overall PVC sheathed size 1.50 sq mm.

2, 3, 4, 5, 6, 7, 10, 12, 14, 16, 19, 24, 29, 30, 37, 44, 48, 52, 54, 61.

500 m drum length
2.Armoured Control Cable PVC Insulated, PVC Inner Armoured with steel wire / strip overall PVC sheathed size 2.50 sq mm.
2, 3, 4, 5, 6, 7, 10, 12, 14, 16, 19, 24, 29, 30, 37, 44, 48, 52, 54, 61.
500 m drum length
Flexible Cables

Flexible Cables to IS:694, suitable for Indoor/Outdoor such as Moving Instruments, Internal Lighting in buildings & various type of home appliances etc. Sheathed/Unsheathed Copper cable to IS:694 suitable for Indoor/Outdoor use such as Light fitting for fix wiring in houses and Industrial use, Panel board fitting etc. The aluminium conductor cables can be used in Fix wiring in houses & Industrial use.

STARCAB Brand PVC Insulated, Sheathed or Unsheathed 650/1100 Volts grade to IS: 694
 
Size
Drum Length
1. 2 core PVC Insulated twin twisted flexible, unsheathed 0.50 sq.mm to 4.00 sq.mm 100 m Coil
2. Single core PVC Insulated unsheathed 0.50 sq.mm to 4.00 sq.mm 100m Coil
3. 2 core, 3 core, 4 core PVC Insulated cores, PVC sheathed round flexible 0.50 sq.mm to 50.00 sq.mm 100m Coil
 

 
Technical Accepted
Test Certificate -

We provide test certificate detailing test results obtained in our factory with every drum that we dispatch.

Bending Radius -

While installation of PVC insulated heavy duty cables of 650/1100 volts grade, bending radius should no be less than the following -

I. Single Core Cables - 15 times the overall diameter of Cables.

II.Multi Core Cables - 12 times the overall diameter of Cables.

Current Ratings

The continous current ratings and the rating factors for PVC insulated Heavy Duty Cables, given here are generally in accordance with IS: 3961(Pt.II)1967.

Basic Assumptions

The current ratings are based on the following installation conditions -

I. Maximum conductor temparature 70° C.

II. Thermal resistivity of soil 150° C cm/w.

III. Thermal resistivity of PVC 650° C cm/w.

IV. Ground Temparature 30° C.

V. Ambient air temparature 40° C.

VI. Depth of laying (to the highest point) of cable laid direct in the ground 75 cm.

Short Circuit Current Rating of Aluminium for 1 Second Duration.



Short Circuit Ratings of Starcab Cables can be calculated by using the following formula
       lsh = KA / sqrt ( t )
where
   lsh - Short circuit current im amps.
   A - Conductor area in sq. mm.
   t - duration of short circuit in second.
   K - 75.80 for Aluminium Cables.
   K - 109.00 for Copper Cables.

Nominal area of conductor in sq.mm.
Short Circuit Current in Kilo Amps.
Aluminium
Copper
1.50
0.11
0.16
2.50
0.19
0.27
4.00
0.30
0.43
6.00
0.45
0.65
10.00
0.76
1.00
16.00
1.20
1.70
25.00
1.90
2.72
35.00
2.63
3.81
50.00
3.56
5.45
70.00
5.14
7.63
95.00
7.14
10.35
120.00
9.01
13.00
150.00
11.10
16.35
185.00
13.90
20.16
240.00
18.50
26.16
300.00
22.90
32.70
400.00
29.30
43.60
500.00
36.90
54.50
Rating factors for Multi-core control cables with number of cores 5 and above.
No of loaded Cores
5
6
7
10
12
14
16
19
24
27
30
37
44
48
52
56
61
Rating factor
0.72
0.67
0.63
0.55
0.52
0.49
0.47
0.44
0.40
0.38
0.37
0.34
0.32
0.30
0.29
0.28
0.27
Rating Factors for variation in ambient air/ground temparature.
Ambient air/ground temparature °C
15
20
25
30
35
40
45
Air
-
-
1.25
1.16
1.09
1.00
0.90
Ground
1.17
1.12
1.06
1.00
0.94
0.87
0.79